Copyright Micropelt

Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 4 Next »

BYTE

BIT RANGE

SIZE

OFFSET

ABBREV.

DETAILS

1

DB0.7…0.0

8

0

CVP

Current Valve Position %

0x00 … 0x64 / 0 … 100%

Res = 1%

2

DB1.7…1.0

8

8

FSRV

Flow Sensor RAW Value °C

0x00 … 0xFF / 0 … 127.5°C

Res = 0.5°C

3

DB2.7…2.0

8

16

FTMP

Flow TEMPERATURE Value °C

0x00 … 0xFF / 0 … 127.5°C

Res = 0.5°C

4

DB3.7…3.0

8

24

ASRV

Ambient Sensor RAW Value °C

0x00 … 0xFF / 0 … 63.75°C

Res = 0.25°C

5

DB4.7…4.0

8

32

ATMP

Ambient TEMPERATURE Value °C

0x00 … 0xFF / 0 … 63.75°C

Res = 0.25°C

6

DB5.7

1

40

 

RESERVED

 

DB5.6

1

41

ES

Energy Storage is low

1 = Battery is low

 

DB5.5

1

42

HA

Harvesting

1 = Harvesting is active

 

DB5.4

1

43

ASF

Ambient Sensor Failure

1 = Sensor Failure

 

DB5.3

1

44

FSF

Flow Sensor Failure

1 = Sensor Failure

 

DB5.2

1

45

RCE

Radio Communication Error

1 = Radio Loss

 

DB5.1

1

46

RSS

Radio Signal Strength

0 = Normal Radio Signal (RSSI is greater than -100 dBm)

1 = Weak Radio Signal (RSSI is less than -100 dBm)

 

DB5.0

1

47

ME

Motor

1 = Motor Error

7

DB6.7…6.0

8

48

STV

Storage Voltage V

0x00 … 0xFF / 0 … 5100mV

Res = 20mV

8

DB7.7…7.0

8

56

ACC

Average Current Consumed

0x00 … 0xFF / 0 … 2550µA

Res = 10µA

9

DB8.7…7.0

8

64

ACG

Average Current Generated

0x00 … 0xFF / 0 … 2550µA

Res = 10µA

10

DB9.7

1

72

OFF

Operating Condition

0 = Device is in Normal Operation and is Active

1 = Device is in Mounting Position and OFF

 

DB9.6

1

73

SFC

Storage Fully Charged

1 = Fully Charged

 

DB9.5

1

74

 

RESERVED

 

DB9.4

1

75

REFC

Reference Run Completed

1 = Successfully Completed

 

DB9.3

1

76

 

RESERVED

 

DB9.2…9.0

3

77

UM

User Mode

As set by the last received Downlink (DB3.3…3.2)

 

0b000

Valve Position %

0b001

RESERVED

0b010

SP Ambient Temperature °C

0b011

Detecting Opening Point

0b100

Slow Harvesting

0b1zz

RESERVED

11

DB10.7…10.0

8

80

UV

User Value according to User Mode

As set by the last received Downlink (DB0.7…0.0)

VALVE %: 0x00 … 0x64 / 0 … 100%

Res = 1%

AMB TEMP: 0x00 … 0x50 / 0 … 40°C

Res = 0.5°C

If Detecting Opening Point or Slow Harvesting, this value is the maximum flow temperature:

MAX FLOW TEMP: 0x00 … 0x84 / 0 … 33°C

Res = 0.25°C


  • No labels