Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.
Comment: port 0x0F for On/OfF

DOWNLINK

BYTE

BIT RANGE

SIZE

OFFSET

ABBREV.ABBREVIATION

DETAILS

1

DB0.7

1

0

ON

Devices will stay on regardless of 6-week Reference Run results

0 = If a 6-week Reference Run fails, device will switch off

1 = Device will stay on regardless of 6-week Reference Run results

DB0.6

1

1

REC

Do a Recalibration Now

1 = Do a Recalibration Now

Regardless of whether device is mounted or unmounted, after a Recalibration the device will continue operating

DB0.5…0.1

5

2

RESERVED

DB0.0

1

7

OFF

Switch OFF the device

1 = Device will move to mounting position and switch OFF

...

Acknowledgement of configuration

BYTE

BIT RANGE

SIZE

OFFSET

ABBREV.ABBREVIATION

DETAILS

1

DB0.7

1

0

ON

Devices will stay on regardless of 6-week Reference Run results

0 = If a 6-week Reference Run fails, device will switch off

1 = Device will stay on regardless of 6-week Reference Run results

DB0.6

1

1

REC

Recalibration was Done

1 = The previous Downlink was an FPORT 0x08 Downlink instructing a Recalibration. Between the previous Downlink and this Uplink, a Recalibration was performed.

Recalibration result is displayed in FPORT 0x01 Uplink bit CAL.

DB0.5…0.1

5

2

RESERVED

DB0.0

1

7

RESERVED

OFF response will be displayed in FPORT 0x01 Uplink bit OFF.

...

Activity

Mounted behaviour

Unmounted behaviour

Device Activation or Reset

(magnet tap or magnet long hold)

Port 1 CAL bit 1 & OFF bit 0

Uplinks sent at 10 second intervals

Port 1 CAL bit 0 & OFF bit 1

No further Uplinks

Long beep

Device switches off

Device goes to 0% but does not find an endstop

Port 1 CAL bit 0 & OFF bit 0

until next successful Recalibration (6-weekly or Downlink)

Port 8 Existing configuration to prevent switch-off

6-week recalibration

Port 1 CAL bit 0 & OFF bit 0

Port 1 CAL bit 1 & OFF bit 0

Port 1 CAL bit 0 & OFF bit 0

until next successful Recalibration (6-weekly or Downlink)

Port 1 Downlink Reference Run

Reference Run performed

Port 1 CAL bit 1 & OFF bit 0

Reference Run performed

Port 1 CAL bit 0 & OFF bit 1

No further Uplinks

Long beep

Device switches off

Port 8 Downlink Recalibration

Recalibration performed

Port 8 0x0F acknowledgement

Port 1 CAL bit 1 & OFF bit 0

Recalibration performed

Port 8 0x0F acknowledgement

Port 1 CAL bit 0 & OFF bit 0

Port 8 Downlink OFF

Port 1 CAL bit 1 & OFF bit 1

Device switches off

...