DOWNLINK
BYTE | BIT RANGE | SIZE | OFFSET | ABBREVIATION | DETAILS | |
1 | DB0.7 | 1 | 0 | ON | Devices will stay on regardless of 6-week Reference Run results 0 = If a 6-week Reference Run fails, device will switch off 1 = Device will stay on regardless of 6-week Reference Run results | |
DB0.6 | 1 | 1 | REC | Do a Recalibration Now 1 = Do a Recalibration Now Regardless of whether device is mounted or unmounted, after a Recalibration the device will continue operating | ||
DB0.5…0.1 | 5 | 2 | RESERVED | |||
DB0.0 | 1 | 7 | OFF | Switch OFF the device 1 = Device will move to mounting position and switch OFF |
DB0.7 setting will be stored in Non-Volatile Memory:
Devices which are instructed to stay on regardless of 6-week Reference Runs will retain this instruction, even when reset with a 5-second magnet hold
Devices which have never received a Port 8 instruction (eg newly produced devices) and which fail a 6-week Reference Run will switch off
UPLINK
Acknowledgement of configuration
BYTE | BIT RANGE | SIZE | OFFSET | ABBREVIATION | DETAILS | |
1 | DB0.7 | 1 | 0 | ON | Devices will stay on regardless of 6-week Reference Run results 0 = If a 6-week Reference Run fails, device will switch off 1 = Device will stay on regardless of 6-week Reference Run results | |
DB0.6 | 1 | 1 | REC | Recalibration was Done 1 = The previous Downlink was an FPORT 0x08 Downlink instructing a Recalibration. Between the previous Downlink and this Uplink, a Recalibration was performed. Recalibration result is displayed in FPORT 0x01 Uplink bit CAL. | ||
DB0.5…0.1 | 5 | 2 | RESERVED | |||
DB0.0 | 1 | 7 | RESERVED OFF response will be displayed in FPORT 0x01 Uplink bit OFF. |
Port 1 Bit 9.4 “REFC” will be renamed to “CAL”:
0 = Failed to Calibrate, 0% may be incorrect
1 = Successful Calibration
Activity | Mounted behaviour | Unmounted behaviour |
Device Activation or Reset (magnet tap or magnet long hold) | Port 1 CAL bit 1 & OFF bit 0 Uplinks sent at 10 second intervals | Port 1 CAL bit 0 & OFF bit 1 No further Uplinks Long beep Device switches off |
Device goes to 0% but does not find an endstop | Port 1 CAL bit 0 & OFF bit 0 until next successful Recalibration (6-weekly or Downlink) | |
Port 8 Existing configuration to prevent switch-off 6-week recalibration | Port 1 CAL bit 0 & OFF bit 0 Port 1 CAL bit 1 & OFF bit 0 | Port 1 CAL bit 0 & OFF bit 0 until next successful Recalibration (6-weekly or Downlink) |
Port 1 Downlink Reference Run | Reference Run performed Port 1 CAL bit 1 & OFF bit 0 | Reference Run performed Port 1 CAL bit 0 & OFF bit 1 No further Uplinks Long beep Device switches off |
Port 8 Downlink Recalibration | Recalibration performed Port 0x0F acknowledgement Port 1 CAL bit 1 & OFF bit 0 | Recalibration performed Port 0x0F acknowledgement Port 1 CAL bit 0 & OFF bit 0 |
Port 8 Downlink OFF | Port 1 CAL bit 1 & OFF bit 1 Device switches off |