...
BYTE | BIT RANGE | SIZE | OFFSET | ABBREVIATION | DETAILS | |
1 | DB0.7…0.0 | 8 | 0 | FADD | Flow Raw Value Offset With 2’s complement Res = 0.25°C | |
0x00 | 0.00 | |||||
0x01 | 0.25 | |||||
0x02 | 0.50 | |||||
… | … | |||||
0x7F | 31.75 | |||||
0x80 | -32.00 | |||||
… | … | |||||
0xFF | -0.25 | |||||
2 | DB1.7…1.0 | 8 | 8 | FMUL | Flow Raw Value Multiplication Res = 0.01°C | |
3 | DB2.7…2.0 | 8 | 16 | NSFNFD | Number of most recent Flow Raw Temperature values to delay by (skip) Clamped to [0..=20] | |
4 | DB3.7…3.0 | 8 | 24 | NMAF | Number of values used in calculation of Flow Moving Average Clamped to [1..=20] | |
5 | DB4.7…4.0 | 8 | 32 | NMAA | Number of values used in calculation of Ambient Moving Average Clamped to [1..=20] | |
6 | DB5.7…5.0 | 8 | 40 | NMAE | Number of values used in calculation of Estimate Moving Average Clamped to [1..=20] | |
7 | DB6.7…6.0 | 8 | 48 | RATO | Ratio Offset Res = 0.01 | |
8 | DB7.7…7.0 | 8 | 56 | POW | Ratio Power Res = 0.01 Default = 0x00 = 1.2 |
...
Mathblock | ||||
---|---|---|---|---|
| ||||
--uriencoded--\begin%7Baligned%7D \text%7BFlow Moving Average%7D(t) = \frac%7B\sum_%7Bi = t - \text%7Bn skip flow%7D - \text%7Bn moving average flow%7D + 1%7D%5e%7Bt - \text%7Bn skip flow%7D%7D%7B\text%7BFlow Sensor Raw Value%7D(i)%7D%7D%7B\text%7Bn moving average flow%7D%7D \\ \text%7BAmbient Moving Average%7D(t) = \frac%7B\sum_%7Bi = t - \text%7Bn moving average ambient%7D + 1%7D%5e%7Bt%7D%7B\text%7BAmbient Sensor Raw Value%7D(i)%7D%7D%7B\text%7Bn moving average ambient%7D%7D \\ \text%7BEstimate%7D(t) = \text%7BAmbient Moving Average%7D(t) * (\frac %7B\text%7BAmbient Moving Average%7D(t)%7D %7B\text%7BFlow Mul%7D * \text%7BFlow Moving Average%7D(t) + \text%7BFlow Offset%7D%7D + \text%7Bratio offset%7D)%5e%7B\text%7Bratio power%7D%7D \\ \text%7BAmbient Temperature%7D(t) = \frac%7B\sum_%7Bi = t - \text%7Bn moving average estimate%7D + 1%7D%5e%7Bt%7D%7B\text%7BEstimate%7D(i)%7D%7D%7B\text%7Bn moving average estimate%7D%7D \end%7Baligned%7D |
Recommended Settings
Environment | Flow Offset | Flow Multiplication | Flow Delay | Flow Moving Average | Estimate Moving Average | Ratio Power |
---|---|---|---|---|---|---|
Small, well-insulated room | 0.0 | 1.0 | Low | 1.0 + small | ||
Large, poorly-insulated room | 0.0 | 1.0 | High | 1.0 + big | ||
Unheated Room is warm | 0.0 | 1.0 | 1.0 + small | |||
Unheated Room is cold | 0.0 | 1.0 | 1.0 + big | |||
Flow Temperature fluctuates | 0.0 | 1.0 | Use to smooth | |||
Estimated Temperature fluctuates | 0.0 | 1.0 | Use to smooth | |||
Device is mounted above an exposed pipe | Use to compensate | Use to compensate |