Copyright Micropelt

Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 3 Next »

DOWNLINK

BYTE

BIT RANGE

SIZE

OFFSET

ABBREVIATION

DETAILS

1

DB0.7…0.0

8

0

FADD

Flow Raw Value Offset

With 2’s complement

Res = 0.25°C

0x00

0.00

0x01

0.25

0x02

0.50

0x7F

31.75

0x80

-32.00

0xFF

-0.25

2

DB1.7…1.0

8

8

 FMUL

Flow Raw Value Multiplication

Res = 0.01°C

3

DB2.7…2.0

8

16

NSF

Number of most recent Flow Raw Temperature values to skip

Clamped to [0..=20]

4

DB3.7…3.0

8

24

NMAF

Number of values used in calculation of Flow Moving Average

Clamped to [1..=20]

5

DB4.7…4.0

8

32

NMAA

Number of values used in calculation of Ambient Moving Average

Clamped to [1..=20]

6

DB5.7…5.0

8

40

NMAE

Number of values used in calculation of Estimate Moving Average

Clamped to [1..=20]

7

DB6.7…6.0

8

48

RATO

Ratio Offset

Res = 0.01

8

DB7.7…7.0

8

56

POW

Ratio Power

Res = 0.01

Default = 0x00 = 1.2

Tip: To get Temperature Estimation details without changing any options, send an empty FPORT 0x08 Downlink.

UPLINK

Same a Downlink, confirming Uplink settings

  • No labels