Info |
---|
Device will only check for a Temperature Drop and respond to the Detection of a Temperature Drop when the Radio Communication Interval is 5 minutes or 10 minutes |
Info |
---|
Device does not take any action upon detection of a temperature drop by default Please set the TDA bits in the downlink (DB0.7…0.6) to take the corresponding action |
DOWNLINK
BYTE | BIT RANGE | SIZE | OFFSET | ABBREVIATION | DETAILS | |
1 | DB0.7…0.6 | 2 | 0 | TDA | Temperature Drop Action Upon Detection of a Temperature Drop: | |
0b00 | Take No Action | |||||
0b01 | RESERVED | |||||
0b10 | close to 0% for 30 minutes and then resume normal operation | |||||
0b11 | close to 0% for 60 minutes and then resume normal operation | |||||
DB0.5 | 1 | 2 | TDB | Upon Resumption of Normal Operation: | ||
0 | Do not Beep | |||||
1 | Beep | |||||
DB0.4 | 1 | 3 | TDP | Temperature Drop Period Activation of Temperature Drop Action after at least: | ||
0 | one temperature drop | |||||
1 | two consecutive temperature drops | |||||
DB0.3…0.0 | 4 | 4 | RESERVED |
...