Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.
Comment: Follow the standard style
Info

Device will only check for a Temperature Drop and respond to the Detection of a Temperature Drop when the Radio Communication Interval is 5 minutes or 10 minutes

Info

Device does not take any action upon detection of a temperature drop by default

Please set the TDA bits in the downlink (DB0.7…0.6) to take the corresponding action

DOWNLINK

BYTE

BIT RANGE

SIZE

OFFSET

ABBREVIATION

DETAILS

1

DB0.7…0.6

2

0

TDA

Temperature Drop Action

Default = 0b00

Upon Detection of a Temperature Drop:

0b00

Take No Action

0b01

RESERVED

0b10

close to 0% for 30 minutes and then resume normal operation

0b11

close to 0% for 60 minutes and then resume normal operation

DB0.5

1

2

TDB

Upon Resumption of Normal Operation:

0

Do not Beep

1

Beep

DB0.4

1

3

TDP

Temperature Drop Period

Activation of Temperature Drop Action after at least:

0

one temperature drop

1

two consecutive temperature drops

DB0.3…0.0

4

4

RESERVED

...