Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

To obtain an estimate of the flow temperature, the The device measures the flow temperature every 5 minutes and calculates the average since the last radio communication. It then adds the user-specified flow offset.

Mathblock
(\text{average since last radio communication}) + \text{offset}

.

The device moves the motor every 60 minutes. To compute the motor movement, the device computes the flow moving average over the last 35 minutes and then applies a Proportional Controller Gain algorithm:.

Mathblock
anchor
alignmentleft

...

--uriencoded--\text%7BNew %25%7D = \text%7BPrevious %25%7D + (\text%7BProportional Controller Gain%7D * (\

...

text%7BSetpoint Flow Temperature%7D - \text%7BFlow Moving Average%7D) * 4)

The default value of P “Proportional Controller Gain” is 31. It can be modified via the downlink packetPort 1 Downlink packet ( Abbreviation: GAIN).