Copyright Micropelt

Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

Version 1 Next »

Parameter

Range

Valve thread

M 30 x 1,5 (adapter available for other types)

Ambient operating temperature

0 - 40°C, max 70% rH

Flow pipe temperature

75°C max

Transportation & storage temperature range

-10 - +45°C, max 70% rH

Max pin stroke (calibration range)

> 5 mm

Operating pin stroke (0-100 %)

2.0 mm typical

Pin Stroke Resolution (defined by EnOcean Equipment Profile A5-20-01)

Steps of 1%

Adjustment speed

0.95 mm/s typical

Stall force

100 N typical

Noise level

~ 30 dB(A)

RF communication interval

According to A5-20-06

RF communication interval

Activation / installation

2 Minutes

(Will revert to A5-20-06 settings after 30 minutes)

Ambient Temperature

Activation / installation

 

Effective Ambient sensor value

(Will revert to approximated value after 30 minutes.  Calibration time in radiator closed situation 3 x 10 Minutes. Start value smoothing = 20°C); requires stable flow temperature when heating is on.

Freeze protection

Below 6ºC, open valve to 95%

Normal operation when T flow > 6°C

0°C when setpoint temperature = 0°C

Window open detection

Yes

Safe position

(following 6 consecutive communication failures)

Internal temperature controller with last valid setpoint °C, otherwise default value 21°C

Will revert to standard operation as soon as radio communication is online again

EnOcean EEP

 

A5-20-06

(Valve Position or Setpoint Temperature)

EnOcean Remote management & Remote commissioning

Yes (Section 9)

DDF (Device description file)

Yes

(Pls. contact Micropelt)

Life cycle status and monitoring capabilities

Yes

(Section 8)

Local offset control

+/- 5°C

(Section 4)

Accuracy of ambient and flow temperature sensor

+/- 0.5 ºC

 

Ambient temperature sensor offset compensation

Default: Automatic Offset compensation

(Configurable through Remote Commissioning)

Energy storage

 

Construed for full year operation and recharged. Immediately ready for use if stored for up to 12 months and at a storage temperature of no more than 40ºC

Energy generation minimum requirement

90 standard heating days per year with T flow >45°C

Battery voltage flag

Battery voltage < 3.1 V

(RF communication interval will be set to 10 minutes)

Radio carrier frequency

868.3 MHz

Maximum radiated power

+1.4 dBm (EN 300220-2:V3.1.1)

Receiver

Category 2 (EN 300 220-1 V3.1.1)

Conformity

CE

  • No labels