Technical Data MVA009


Copyright Micropelt

Technical Data MVA009

Parameter

Range

Valve thread

M 30 x 1,5 (adapter available for other types)

Ambient operating temperature

0 - 40°C, max 70% rH

Flow pipe temperature

75°C max

Transportation & storage temperature range

-10 - +45°C, max 70% rH

Ingress protection

IP4X according to DIN EN / IEC 60529

Weight

270 g

Dimensions

Ø 55 mm, length 82 mm
(Length with valve connector 97 mm)

Max pin stroke (calibration range)

> 5 mm

Operating pin stroke (0-100 %)

2.0 mm typical

Pin Stroke Resolution (defined by EnOcean Equipment Profile A5-20-01)

Steps of 1%

Adjustment speed

0.95 mm/s typical

Stall force

100 N typical

Noise level

~ 30 dB(A)

RF communication interval

According to A5-20-06

RF communication interval
Activation / installation

2 Minutes
(Will revert to A5-20-06 settings after 30 minutes)

Ambient Temperature
Activation / installation

 

Effective Ambient sensor value
(Will revert to approximated value after 30 minutes.  Calibration time in radiator closed situation 3 x 10 Minutes. Start value smoothing = 20°C); requires stable flow temperature when heating is on.

Freeze protection

Below 6ºC, open valve to 95%
Normal operation when T flow > 6°C
0°C when setpoint temperature = 0°C

Window open detection

Yes

Safe position

(following 6 consecutive communication failures)

Internal temperature controller with last valid setpoint °C, otherwise default value 21°C
Will revert to standard operation as soon as radio communication is online again

EnOcean EEP

A5-20-06
(Valve Position or Setpoint Temperature)

EnOcean Remote management & Remote commissioning

Yes (Section 9)

DDF (Device description file)

Yes (Pls. contact Micropelt)

Life cycle status and monitoring capabilities

Yes

Local offset control

+/- 5°C

Accuracy of ambient and flow temperature sensor

+/- 0.5 ºC

Ambient temperature sensor offset compensation

Default: Automatic Offset compensation (Configurable through Remote Commissioning)

Energy storage

 

Construed for full year operation when sufficiently charged in winter season. Pre-charged, immediately ready for use if stored for up to 12 months and at a storage temperature of no more than 40ºC

Energy generation minimum requirement

90 standard heating days per year with T flow >45°C

Battery voltage flag

Battery voltage < 3.1 V (RF communication interval will be set to 10 minutes)

Radio carrier frequency

868.3 MHz

Maximum radiated power

+1.4 dBm (EN 300220-2:V3.1.1)

Receiver

Category 2 (EN 300 220-1 V3.1.1)

Conformity

CE

Related content

Technische Daten MVA009
Technische Daten MVA009
Read with this
Technical Data MVA008
Technical Data MVA008
More like this
Performance Data
Performance Data
More like this
MVA009 Quickstart Guide
MVA009 Quickstart Guide
More like this
MLR003FiEU61-AR-K Title Page
MLR003FiEU61-AR-K Title Page
More like this
Communication Profile
Communication Profile
More like this