FPort Number

Type of operation

Payload length

Description

Comments

0x00

MAC Commands

8 Bytes

RESERVED

0x01

  • Valve position % mode

  • Temperature setpoint mode (°C) with ambient or external temperature sensor

Downlink:

6 Bytes

Uplink:

11 Bytes

  • Actuator operation mode with valve position %

  • Self-regulation mode using the requested ambient setpoint temperature




Strongly recommended to always use an external temperature sensor

0x02

Report:

  • REV

  • Hardware Version

  • Firmware Version

Downlink:

0 Bytes

Uplink:

6 Bytes

Request:

  • REV

  • Hardware Version

  • Firmware Version

Only supported in REV2.0

0x03 

 Motor operating range

Downlink:

1 Byte

Uplink:

1 Byte

Configure motor operating range (mm)

Only supported in REV2.0

0x04 

 LoRa Spread Factor

Downlink:

1 Byte

Uplink:

1 Byte

Configure LoRa spread factor

Only supported in REV2.0

0x05

Slow Harvesting (SH) and valve Opening Point Detection (OPD)

Downlink:

1 Byte

Uplink:

1 Byte

  • Activate, configure, and deactivate OPD and SH

  • View status of OPD and SH

Only supported in REV2.0


  • No labels