DOWNLINK
BYTE | BIT RANGE | SIZE | OFFSET | ABBREVIATION | DETAILS | |
1 | DB0.7…0.0 | 8 | 0 | FADD | Flow Raw Value Offset With 2’s complement Res = 0.25°C | |
0x00 | 0.00 | |||||
0x01 | 0.25 | |||||
0x02 | 0.50 | |||||
… | … | |||||
0x7F | 31.75 | |||||
0x80 | -32.00 | |||||
… | … | |||||
0xFF | -0.25 | |||||
2 | DB1.7…1.0 | 8 | 8 | FMUL | Flow Raw Value Multiplication Res = 0.01°C | |
3 | DB2.7…2.0 | 8 | 16 | NMAF | Number of values used in calculation of Flow Moving Average Clamped to [1..=20] | |
4 | DB3.7…3.0 | 8 | 24 | NMAA | Number of values used in calculation of Ambient Moving Average Clamped to [1..=20] | |
5 | DB4.7…4.0 | 8 | 32 | NMAE | Number of values used in calculation of Estimate Moving Average Clamped to [1..=20] | |
6 | DB5.7…5.0 | 8 | 40 | RATO | Ratio Offset Res = 0.01 | |
7 | DB6.7…6.0 | 8 | 48 | POW | Ratio Power Res = 0.01 Default = 0x00 = 1.2 |
Tip: To get Temperature Estimation details without changing any options, send an empty FPORT 0x08 Downlink.
UPLINK
Same a Downlink, confirming Uplink settings