Copyright Micropelt

Skip to end of metadata
Go to start of metadata

You are viewing an old version of this content. View the current version.

Compare with Current View Version History

« Previous Version 7 Next »

Defaults

Changed through downlink

P coefficient

20

15

I coefficient

1,5

1,5

D coefficient

0

0

Correction factor z

D coefficient when closed

0

0

Closed percent

0

0

Offset percent

0

0

Style

Standard Style

Unchanged = Default

Integral unwind (do_back calculate)

False

Unchanged = Default

Motor operating range

1.872 mm

Unchanged = Default

Firmware

2024.08.08.02

Device is running with “z“ factor set to 0,1

Flow temperature is increased to 65°

2408011-15_Rev2.bZCC_screencapture-dashboard-deos-ag-20240815-152257.png

FTMP (flow smoothened) = (0,2C + 1,2Ct-1 + 1Ct-2 +0,8Ct-3 + 0,6Ct-4 + 0,3Ct-5  +0,1Ct-6 ) / 4,2

Weighted smoothing of the last 7 values.

Division method

With additional correction, the influence of which depends on how much the flow values ​​have changed from one measured value to the next.

Cc (Flow corrected) = if (Cs - z * (Cs - 0,5 * (Cst-3+Cst-4)) < B

      then ( B )

      else (Cs - z * (Cs - 0,5 * (Cst-3+Cst-4))

The ATMP value is the Ambient Estimate calculated based on your formula ATMP = B * ( B/ Cc) ^ 1,2

where B = Ambient Raw

Cc = Flow corrected

  • No labels