Copyright Micropelt

Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 2 Next »

Device will only check for a Temperature Drop and respond to the Detection of a Temperature Drop when the Radio Communication Interval is 5 minutes or 10 minutes

DOWNLINK

BYTE

BIT RANGE

SIZE

OFFSET

ABBREVIATION

DETAILS

1

DB0.7…0.6

2

0

TDA

Temperature Drop Action

Upon Detection of a Temperature Drop:

0b00

Take No Action

0b01

RESERVED

0b10

close to 0% for 30 minutes and then resume normal operation

0b11

close to 0% for 60 minutes and then resume normal operation

DB0.5

1

2

TDB

Upon Resumption of Normal Operation:

0

Do not Beep

1

Beep

DB0.4

1

3

TDP

Temperature Drop Period

Activation of Temperature Drop Action after at least:

0

one temperature drop

1

two consecutive temperature drops

DB0.3…0.0

4

4

RESERVED

UPLINK

BYTE

BIT RANGE

SIZE

OFFSET

ABBREVIATION

DETAILS

1

DB0.7…0.6

2

0

TDA

Temperature Drop Action

Upon Detection of a Temperature Drop, device will:

0b00

Take No Action

0b01

RESERVED

0b10

close to 0% for 30 minutes and then resume normal operation

0b11

close to 0% for 60 minutes and then resume normal operation

DB0.5

1

2

TDB

Upon Resumption of Normal Operation, device will:

0

not Beep

1

Beep

DB0.4

1

3

TDP

Temperature Drop Period

Activation of Temperature Drop Action after at least:

0

one temperature drop

1

two consecutive temperature drops

DB0.3…0.1

3

4

RESERVED

DB0.0

1

7

TDD

A Temperature Drop has been Detected

0

No Detection

1

Detection

Ambient RAW value dropped by >= 1.5°C during the last 10 minutes

  • No labels