BYTE | BIT RANGE | SIZE | OFFSET | ABBREV. | DETAILS | ||
1 | DB0.7…0.0 | 8 | 0 | SPV | Set Point Value according to User Mode VALVE %: 0x00 … 0x64 / 0 … 100% Res = 1% FLOW TEMP: 0x00 … 0xA0 / 0 … 80°C 0x00 = Default = 0x6E = 55°C Res = 0,5°C | ||
2 | DB1.7…1.0 | 8 | 8 |
| RESERVED Set to 0x00 | ||
3 | DB2.7…2.0 | 8 | 16 | SSV | Set Safety Value according to safety mode FLOW TEMP: 0x00 … 0xA0 / 0 … 80°C 0x00 = Default = 0x6E = 55°C Res = 0,5°C VALVE %: 0x00 … 0x64 / 0 … 100% Res = 1% | ||
4 | DB3.7 | 1 | 24 |
| RESERVED | ||
| DB3.6…3.4 | 3 | 25 | RCI | Radio Communication Interval 0b010 = Default = 60 minutes | ||
0b000 | 10 minutes | ||||||
0b001 | 5 minutes | ||||||
0b010 | 60 minutes | ||||||
0b011 | 120 minutes | ||||||
0b100 | 480 minutes | ||||||
0b1zz | RESERVED | ||||||
| DB3.3…3.2 | 2 | 28 | UM | User Mode 0b01 = Default = SP Flow Temperature | ||
0b00 | Valve Position % | ||||||
0b01 | SP Flow Temperature °C | ||||||
0b10 | RESERVED | ||||||
0b11 | RESERVED | ||||||
| DB3.1…3.0 | 2 | 30 | SM | Safety Mode 0b01 = Default = SP Flow Temperature | ||
0b00 | RESERVED | ||||||
0b01 | SP Flow Temperature °C | ||||||
0b10 | Valve Position % | ||||||
0b11 | RESERVED | ||||||
5 | DB4.7…4.4 | 4 | 32 | FSOC | Offset Compensation Flow Sensor °C -8°C … +7°C | ||
0x00 | +5°C (default) | ||||||
0x01 | +1°C | ||||||
0x02 | +2°C | ||||||
0x03 | +3°C | ||||||
0x04 | +4°C | ||||||
0x05 | +5°C | ||||||
0x06 | +6°C | ||||||
0x07 | +7°C | ||||||
0x08 | -8°C | ||||||
0x09 | -7°C | ||||||
0x0A | -6°C | ||||||
0x0B | -5°C | ||||||
0x0C | -4°C | ||||||
0x0D | -3°C | ||||||
0x0E | -2°C | ||||||
0x0F | -1°C | ||||||
| DB4.3…4.0 | 4 | 36 |
| RESERVED | ||
6 | DB5.7 | 1 | 40 | REF | Do Reference Run now Default = 0 | ||
| DB5.6…5.5 | 2 | 41 | GAIN | Proportional Controller Gain 0b10 = Default = 1 | ||
0b00 | 3 | ||||||
0b01 | 4 | ||||||
0b10 | 1 | ||||||
0b11 | 2 | ||||||
| DB5.4…5.0 | 5 | 43 |
| RESERVED |