MLR003R: Operating Modes

 

Installation cycle

Standard

operation

Idle state

Radio failure

Forced heating

Freeze Protection

Comments

 

Valve target %

Or

Room target temperature

 

Phases between monitoring, communicating, and motor movement

Uplinks not received by the gateway

Valve opens to 50%

(or remains in current position if current position is 50%)

Valve opens to 95%

(or remains in current position if current position is 95%)

Trigger

Magnetic switch.

Join accept

from Gateway,

& Device is mounted

Internal timer

Internal timer

From activation:

No Gateway connect

From standard operation:

3 consecutive Gateway communication failures (9x RCE)

Battery voltage < 2.2V

Flow sensor raw temperature

6°C

Radio communication interval (RCI)

10 seconds for 5 minutes

5 minutes

10 minutes

60 minutes

120 minutes

480 minutes

OFF

Three times 30 seconds

Then once 2 minutes

Then 60 minutes

OFF

OFF

Dynamic change of communication interval

No

Yes

No

No

No

No

Sensors

(flow, ambient)

Active, every 10 seconds

Active

OFF

 

Active

OFF

Active, every

2 minutes

Freeze protection

Active, every 10 seconds

Active, every 150 seconds

OFF

Active, every 150 seconds

OFF

Active

Motor operation

Reference run.

Then active, every 10 seconds

Setpoint Ambient Temperature: Active, every 5 minutes

Valve Position: According to radio communications

OFF

Active, every 5 minutes

OFF

OFF

Monitoring of battery

Active, every 10 seconds

Active

OFF

Active

Active, every 12 hours

Active, every
2 minutes

Internal temperature controller

If User Mode is Setpoint Ambient Temperature: active

If User Mode is Setpoint Ambient Temperature: active

OFF

If Safety Mode is Setpoint Ambient Temperature: active

OFF

OFF

Default upon activation and no downlinks

Setpoint Ambient Temperature 19°C

Setpoint Ambient Temperature 19°C

RCI 10 minutes

 

Setpoint Ambient Temperature 19°C

 

 