MLR003F: Operating Modes
 | Installation cycle | Standard operation | Idle state | Radio failure | Forced heating | Freeze Protection |
Comments |  | Valve target % Or Flow target temperature  | Phases between monitoring and communicating | Uplinks not received by the gateway | Valve opens to 50% (or remains in current position if current position is 50%) | Valve opens to 95% (or remains in current position if current position is 95%) |
Trigger | Magnetic switch. Join accept from Gateway, & Device is mounted | Internal timer | Internal timer | From activation: No Gateway connect From standard operation: 3 consecutive Gateway communication failures | Battery voltage < 2.2V | Flow sensor raw temperature 6°C |
Radio communication interval (RCI) | 10 seconds for 5 minutes | 15 minutes 60 minutes 120 minutes 480 minutes | OFF | 60 minutes | OFF | OFF |
Dynamic change of communication interval | No | Yes | No | No | No | No |
Sensors (flow, ambient) | Active, every 10 seconds | Active | OFF Â | Active | OFF | Active, every 2 minutes |
Freeze protection | Active, every 10 seconds | Active, every 150 seconds | OFF | Active, every 150 seconds | OFF | Active |
Motor operation | Reference run. Then active, every 10 seconds | Active, according to Radio Communication | OFF | Active | OFF | OFF |
Monitoring of battery | Active, every 10 seconds | Active | OFF | Active | Active, every 12 hours | Active, every 2 minutes |
Internal temperature controller | If User Mode is Setpoint Flow Temperature: active | If User Mode is Setpoint Flow Temperature: active | OFF | If Safety Mode is Setpoint Flow Temperature: active | OFF | OFF |
Default upon activation and no downlinks | Setpoint Flow Temperature 55°C | Setpoint Flow Temperature 55°C RCI 60 minutes |  | Setpoint Flow Temperature 55°C |  |  |