MLR003R Feature list


Copyright Micropelt

MLR003R Feature list

 

 Product

 Feature

Description

FPORT

Keywords

Benefits

MLR003R

Operating mode setpoint ambient temperature °C w/o external room temperature sensor value °C

Device receives °C setpoint temperature value

0x01

Room temperature control accuracy

Adjustable PI control

Operates on its optimized internal PI-controller with adjustable parameters. No external room sensor required.

MLR003R

Operating mode setpoint ambient temperature °C with external room temperature sensor value °C

Device receives °C setpoint temperature value plus room sensor value

0x01

Room temperature control accuracy

Adjustable PI control

Motor travel

Operates on its optimized internal PI-controller with adjustable parameters and reduced motor travel.

MLR003R

External Temperature Sensor expiry

Decide for how long the MLR003 is using its last received external room sensor value.

 

0x09

External Temperature Sensor expiry

If a Room Temperature is sent by Downlink, continue using it until: a) new Room Temperature is sent by Downlink, or until b) the Device loses Gateway communication, or until c) individual time setting

MLR003R

PI(D) control closed percent

Adjustable PI parameter Closed Percent (Minimum percent that device will close to)

0x07

PI Closed Percent

Eliminate the dead are from 0% to effective water flow (valve opening point), see FPORT 0x05

MLR003R

PI(D) control offset percent

Adjustable PI parameter Offset percent (Percentage Offset to be added to PID Output)

0x07

PI Offset Percent

 

MLR003R

Operation with external temperature sensor

Device receives °C setpoint temperature value

0x0a

External room sensor

Device receives its room sensor value only on Byte 1. Reduced payload size.

MLR003R

Operating mode valve Position %

Device receives valve position % values from an external temperature controller

0x01

Room temperature control accuracy

 When external PI room temperature control is used from e.g. existing building automation

MLR003R

Internal flow sensor measurement

Device receives °C flow temperature value

0x01

Internal flow sensor

Useful to analyze flow distribution in buildings.

MLR003R

Battery measurement

Device returns its battery voltage with standard LoRaWAN MAC command …

0x00

Battery status

Battery status

MLR003R

Energy management and harvesting

Device measures its averaged consumption as well as generation between active periods 

0x01

Energy management, Harvesting

Energy status

MLR003R

Adjustable motor travel distance

Mass flow reduction through reduced motor travel distance (resolution increases with reduced mm operating range over 0…100%)

0x03

Hydronic balancing

Allows hydronic balancing.

Useful in unbalanced radiator and uncontrolled/over dimensioned flow temperature installations.

MLR003R

Local ambient temperature measurement

Flow raw offset correction

0x08

Smart and adjustable local ambient measurement

 

MLR003R

Opening point detection

Effective valve body opening point detection

0x05

Effective valve body opening point

 Can be used as “closed percent” input to PI(D) controller FPORT 0x07

MLR003R

Slow harvesting

Trickle recharge the internal storage w/o heating the room

0x05

 Slow harvesting

A way to keep the internal storage charged when operating devices in unheated rooms 

MLR003R

Temperature drop detection

Device returns temperature drops

0x06

Adjustable open window detection

Adjustable temperature drop detection can be used to identify open windows

MLR003R

Freeze protection

Device continuously measure against low temperature on its flow sensor to prevent water freeze and radiator/pipe damages

0x01

Precise freeze protection flow sensor

Prevent from water freeze and radiator/pipe damages

MLR003R

Adjustable Device On/Off

Ability to switch off the device when e.g. unmounted  

0x0f

On/Off

 