Technical Data MVA008


Copyright Micropelt

Technical Data MVA008

Parameter

 

Range

 

Valve thread

M 30 x 1,5 (adapter available for other types)

Ambient operating temperature

0 to 40°C, max 70% rH

Flow pipe temperature

75°C max

Transportation & storage temperature range

-10 to +45°C, max 70% rH

Max pin stroke (calibration range)

> 5 mm

Operating pin stroke (0-100 %)

2.5 mm typical

Pin Stroke Resolution (defined by EnOcean Equipment Profile A5-20-01)

Steps of 1% (smallest executable position change must be 3% from current physical position)

Adjustment speed

0.95 mm/s typical

Stall force

100 N typical

Noise level

< 30 dB(A)

RF communication interval

Default: Automatic 2/5/10 minutes
Other settings through Remote Commissioning

Activation and debug

RF communication interval

~ 10 sec
(will revert to the default 10 minutes after 10 minutes)

Antifreeze

Below 6ºC, open valve to 95%

Safe position

(following 6 consecutive communication failures)

Internal temperature controller with 21°C target value
Will revert to standard operation as soon as radio communication is online again

EnOcean EEP and operating mode

A5-20-01 (Valve Position and SetTemp)

EnOcean Remote management & Remote commissioning capability

Yes

Accuracy of internal ambient temperature sensor

+/- 0.5 ºC 

Offset of internal ambient temperature sensor

Default: Automatic offset correction
Fixed offset settings through Remote Commissioning

Energy storage

Construed for full year operation when sufficiently charged in winter season. Pre-charged, immediately ready for use if stored for up to 12 months and at a storage temperature of no more than 40ºC

Energy generation minimum requirement

90 standard heating days per year
@ >45ºC flow pipe temperature and 8h heating
@ 10minutes duty cycle and steps of 10% per cycle

Battery voltage flag

Battery voltage < 3.1 V (prefer more margin as this level is also used to reset communication interval): Set battery-low flag and reset RF communication interval to default 10 min

Radio carrier frequency

868.3 MHz

Maximum radiated power

+1.4 dBm (EN 300220-2: V3.1.1)

Receiver

Category 2 (EN 300 220-1 V3.1.1)

Conformity

CE

Related content

Technical Data MVA009
Technical Data MVA009
More like this
Performance Data
Performance Data
More like this
MVA009 Quickstart Guide
MVA009 Quickstart Guide
More like this
Technische Daten MVA008
Technische Daten MVA008
More like this
MVA008 Quickstart Guide
MVA008 Quickstart Guide
More like this
MLR003F: Operating Modes
MLR003F: Operating Modes
More like this